ÖLFLEX® CLASSIC 128 CH BK 0,6/1 KV 12G1,5
Power and control cable; 12G1.5; U0/U: 0,6/1 kV; HFFR; Core identification: Numbers; Shielded; Flexible
Benefits
- Easy handling and installation due to the flexible variant.
- Space-saving due to small outer diameters.
- Halogen free and highly flame retardant materials reduce the risk of flame propagation, high smoke density and toxic flue gases in the event of a fire.
- Ideal protection against electromagnetic interference thanks to copper screening braiding with a high degree of coverage.
- High electrical safety thanks to 4000 V test voltage.
Applications
- For structured building cabling for fulfilling special fire protection requirements.
- For universal use for wiring machine-internal and cross-plant control circuits.
- For circuits that require a higher nominal voltage due to their installation.
- Especially for environments where electromagnetic compatibility (EMC) is required.
- For fixed installation and occasional flexing without tensile strain.
- Can be used in dry and damp environments.
- Suitable for medium mechanical stress.
- Suitable for outdoor use, subject to the temperature range.
Technical Attributes
General Information
Brand
ÖLFLEX®
Product type
Power and control cable
Weight
498 kg/km
Copper index
238.300 kg/km
copper index (lb)
1601.310 lb/10,000 ft
Electrical Characteristics
Nominal voltage
U0/U: 0,6/1 kV AC rms according to IEC
test voltage conductor/conductor
4 kV
Test voltage core/screening
2 kV
Max. conductor resistance at 20°C
13.3 Ω/km
Product Design
Cable dimension
12G1.5
Conductor cross-section (mm2)
1.5 mm²
Conductor material
Bare Copper
Conductor design
IEC 60228 class 5: fine-wire
Including protective conductor
Yes
Number of cores
12
Stranding type
Layered Stranding
Wrapping over stranding
Halogen-free plastic film
Shielded
Yes
Type of overall screen
Tin-plated copper braiding
Nominal outer diameter
16.3 mm
Shape of cable
Round
Core insulation base material
Halogen-free compound
Core insulation base material, shortname
HFFR
Base material of outer sheath
Halogen-free compound
Base material of outer sheath, shortname
HFFR
With reinforced cable insulation
No
Cable insulation colour
black
Core identification
Numbers
Core colour code
VDE 0293-1EN 50334
Product Characteristics
Application area
FlexibleFixed Installation
For torsional load
No
Minimum bending radius, fixed installation
6 x outer diameter
Minimum bending radius in mm, stationary
97.8 mm
Minimum bending radius, occasionally moved
20 x outer diameter
Minimum bending radius in mm, occasionally flexing
326.0 mm
temperature, fixed installation
-40 °C to 80 °C
Temperature, occasionally moved
-5 °C to 70 °C
Flame-retardant
Yes
Flame retardance according to
IEC 60332-3-24
Low smoke density according to
IEC 61034-2
Low toxicity of combustion gases
EN 50306-1 (≤ 3)
corrosiveness of combustion gases according to
IEC 60754-2
UV-resistant
Yes
UV-resistant according to
DIN EN ISO 4892-2 method AEN 50525-1 (cables with a black sheath are suitable for permanent outdoor use)EN 50618EN 50620
Ozone resistant
Yes
Ozone-resistant according to
EN 50396, method B
Halogenfree
Yes
Zero halogen according to
IEC 60754-1
Oil-resistant
No
PWIS-free
Yes
PWIS-free according to
VDMA 24364-B2-L
Certifications and Standards
CE marked
Yes
EAC certified
Yes
EAC certification number
ЕАЭС RU С-DE.АЮ64.В.00091/19
UL recognised
No
UL listed
No
cUR recognized
No
cUL listed
No
CSA certified
No
VDE certified
No
DNV-certified
No
CPR fire class
Eca
Flame retardance tested according to UN/ECE-R118
No
Tested for fire protection for railway vehicles
No
Documentation
-
Downloads
Further Links
-
Notes
- Photographs and graphics are not to scale and do not represent detailed images of the respective products.
- Unless specified otherwise, the product values shown are rated values at room temperature. You can receive further values, such as tolerances, upon request if they are available and have been released for publication.
Product Family List
All articles from ÖLFLEX® CLASSIC 128 CH BK 0,6/1 kV
Article number | Number of cores | Including protective conductor | Conductor cross-section (mm2) | Copper index | Weight | CPR fire class | |
---|---|---|---|---|---|---|---|
1123557 | 2 | No | 1 mm² | 39.500 kg/km | 107 kg/km | Eca | |
1123558 | 3 | Yes | 1 mm² | 51.000 kg/km | 129 kg/km | Eca | |
1123559 | 4 | Yes | 1 mm² | 62.800 kg/km | 153 kg/km | Eca | |
1123560 | 5 | Yes | 1 mm² | 76.000 kg/km | 181 kg/km | Eca | |
1123561 | 7 | Yes | 1 mm² | 97.200 kg/km | 220 kg/km | Eca | |
1123562 | 12 | Yes | 1 mm² | 169.100 kg/km | 343 kg/km | Eca | |
1123564 | 25 | Yes | 1 mm² | 315.500 kg/km | 667 kg/km | Eca | |
1123565 | 2 | No | 1.5 mm² | 53.200 kg/km | 135 kg/km | Eca | |
1123566 | 3 | Yes | 1.5 mm² | 69.500 kg/km | 164 kg/km | Eca | |
1123567 | 4 | Yes | 1.5 mm² | 86.500 kg/km | 199 kg/km | Eca | |
1123568 | 5 | Yes | 1.5 mm² | 104.300 kg/km | 236 kg/km | Eca | |
1123569 | 7 | Yes | 1.5 mm² | 136.500 kg/km | 292 kg/km | Eca | |
1123570 | 12 | Yes | 1.5 mm² | 238.300 kg/km | 498 kg/km | Eca | |
1123571 | 18 | Yes | 1.5 mm² | 355.400 kg/km | 700 kg/km | Eca | |
1123573 | 2 | No | 2.5 mm² | 79.400 kg/km | 176 kg/km | Eca | |
1123574 | 3 | Yes | 2.5 mm² | 106.100 kg/km | 218 kg/km | Eca | |
1123575 | 4 | Yes | 2.5 mm² | 134.300 kg/km | 268 kg/km | Eca | |
1123576 | 5 | Yes | 2.5 mm² | 158.300 kg/km | 322 kg/km | Eca | |
1123577 | 7 | Yes | 2.5 mm² | 225.000 kg/km | 411 kg/km | Eca | |
1123578 | 12 | Yes | 2.5 mm² | 383.600 kg/km | 704 kg/km | Eca | |
1123579 | 18 | Yes | 2.5 mm² | 548.900 kg/km | 1058 kg/km | Eca | |
1123580 | 25 | Yes | 2.5 mm² | 761.700 kg/km | 1449 kg/km | Eca | |
1123582 | 4 | Yes | 4 mm² | 211.900 kg/km | 357 kg/km | Eca | |
1123583 | 5 | Yes | 4 mm² | 250.300 kg/km | 434 kg/km | Eca | |
1123584 | 3 | Yes | 6 mm² | 232.100 kg/km | 372 kg/km | Eca | |
1123585 | 4 | Yes | 6 mm² | 298.500 kg/km | 472 kg/km | Eca | |
1123586 | 5 | Yes | 6 mm² | 356.100 kg/km | 611 kg/km | Eca |