N2XS2Y 1x185 RM/25 6/10kV
Medium-voltage cable; 1x185 RM; U0/U: 6/10 kV; Bare Copper; PE; Shielded; VDE certified; Fixed Installation
Benefits
- VDE-certified cable with ◁VDE▷ testing mark for proven reliability and quality according to VDE 0276-620.
- Robust during installation and operation thanks to robust PE outer sheath.
- Cross-linked conductive layers above and below the core insulation prevent partial discharges and enable constant operational safety.
- Available in conductor cross-sections up to 630 mm2.
- Available in voltage classes 6/10 (12) kV, 12/20 (24) kV and 18/30 (36) kV.
Applications
- Suitable for energy distribution in medium-voltage networks.
- For fixed installation in water, air and earth. In the ground, the minimum installation depth without additional, suitable underground protection is 0.6 m, and at least 0.8 m under roads (according to HD 620/VDE 0276-620 Part 10-C (point 4)).
- Also suitable for indoor installation and closed installation ducts for energy supply company, industrial and distribution networks, but not flame-retardant according to IEC 60332-1.
- Suitable for high mechanical stress due to the PE outer sheath.
- Suitable for outdoor use.
- Use at temperatures up to -40°C possible.
Technical Attributes
General Information
Product type
Medium-voltage cable
Weight
2335 kg/km
Copper index
2059.000 kg/km
copper index (lb)
13835.913 lb/10,000 ft
Electrical Characteristics
Nominal voltage
U0/U: 6/10 kV AC rms according to IEC
Test voltage
15 kV
Current rating according to
VDE 0276-620
Max. conductor resistance at 20°C
0.0991 Ω/km
Product Design
N-German standard cables
N2XS2Y
Conductor count/size
1x185 RM/25
Conductor cross-section (mm2)
185 mm²
Conductor material
Bare Copper
Conductor design
IEC 60228 class 2: multi-wire
Conductor shape
Round
Conductor short form
1x185 RM
Number of cores
1
Shielded
Yes
Type of overall screen
Copper wires with cross-conductor copper spiral
Min. outer diameter
31 mm
Max. outer diameter
37 mm
Shape of cable
Round
Core insulation base material
Cross-linked polyethylene
Core insulation base material, shortname
XLPE
Base material of outer sheath
Polyethylene
Base material of outer sheath, shortname
PE
Cable insulation colour
black
Product Characteristics
Application area
Fixed Installation
Suitable for underground installation
directin cable trenchin protective cable conduit
Minimum bending radius, fixed installation
15 x outer diameter
Minimum bending radius in mm, stationary
555.0 mm
temperature, fixed installation
-40 °C to 90 °C
Installation temperature min.
-20 °C
Flame-retardant
No
UV-resistant
Yes
UV-resistant according to
EN 50525-1 (cables with a black sheath are suitable for permanent outdoor use)
Halogenfree
Yes
Zero halogen according to
IEC 60754-1
Oil-resistant
No
Longitudinally watertight
No
Laterally watertight
No
Certifications and Standards
CE marked
No
VDE certified
Yes
Product standard VDE
VDE 0276-620
Flame retardance tested according to UN/ECE-R118
No
Documentation
-
Notes
- Photographs and graphics are not to scale and do not represent detailed images of the respective products.
- Trade product, not a LAPP product.
- Unless specified otherwise, the product values shown are rated values at room temperature. You can receive further values, such as tolerances, upon request if they are available and have been released for publication.
Product Family List
All articles from N2XS2Y
Article number | Conductor short form | Nominal voltage | Min. outer diameter | Copper index | Weight | |
---|---|---|---|---|---|---|
1550067 | 1x240 RM | U0/U: 6/10 kV AC rms according to IEC | 33 mm | 2587.000 kg/km | 2885 kg/km | |
1552041 | 1x70 RM | U0/U: 12/20 kV AC rms according to IEC | 30 mm | 854.000 kg/km | 1289 kg/km | |
1552047 | 1x150 RM | U0/U: 12/20 kV AC rms according to IEC | 33 mm | 1723.000 kg/km | 2153 kg/km | |
1552068 | 1x35 RM | U0/U: 12/20 kV AC rms according to IEC | 27 mm | 518.000 kg/km | 914 kg/km | |
1552069 | 1x50 RM | U0/U: 12/20 kV AC rms according to IEC | 28 mm | 662.000 kg/km | 1049 kg/km | |
1552070 | 1x70 RM | U0/U: 6/10 kV AC rms according to IEC | 25 mm | 854.000 kg/km | 1123 kg/km | |
3028167 | 1x185 RM | U0/U: 18/30 kV AC rms according to IEC | 40 mm | 2059.000 kg/km | 2802 kg/km | |
3036224 | 1x50 RM | U0/U: 18/30 kV AC rms according to IEC | 32 mm | 662.000 kg/km | 1260 kg/km | |
38001000 | 1x50 RM | U0/U: 6/10 kV AC rms according to IEC | 24 mm | 662.000 kg/km | 900 kg/km | |
38107029 | 1x150 RM | U0/U: 6/10 kV AC rms according to IEC | 29 mm | 1723.000 kg/km | 1966 kg/km | |
38107786 | 1x35 RM | U0/U: 6/10 kV AC rms according to IEC | 23 mm | 518.000 kg/km | 770 kg/km | |
38107787 | 1x70 RM | U0/U: 6/10 kV AC rms according to IEC | 25 mm | 1238.000 kg/km | 1450 kg/km | |
38107788 | 1x95 RM | U0/U: 6/10 kV AC rms according to IEC | 26 mm | 1094.000 kg/km | 1384 kg/km | |
38107789 | 1x120 RM | U0/U: 6/10 kV AC rms according to IEC | 28 mm | 1334.000 kg/km | 1623 kg/km | |
38107790 | 1x185 RM | U0/U: 6/10 kV AC rms according to IEC | 31 mm | 2059.000 kg/km | 2335 kg/km | |
38107791 | 1x300 RM | U0/U: 6/10 kV AC rms according to IEC | 36 mm | 3163.000 kg/km | 3480 kg/km | |
38107792 | 1x400 RM | U0/U: 6/10 kV AC rms according to IEC | 38 mm | 4234.000 kg/km | 4381 kg/km | |
38107793 | 1x500 RM | U0/U: 6/10 kV AC rms according to IEC | 41 mm | 5194.000 kg/km | 5382 kg/km | |
38107794 | 1x120 RM | U0/U: 12/20 kV AC rms according to IEC | 32 mm | 1334.000 kg/km | 1802 kg/km | |
38107795 | 1x185 RM | U0/U: 12/20 kV AC rms according to IEC | 35 mm | 2059.000 kg/km | 2533 kg/km | |
38107796 | 1x240 RM | U0/U: 12/20 kV AC rms according to IEC | 38 mm | 2587.000 kg/km | 3096 kg/km | |
38107797 | 1x300 RM | U0/U: 12/20 kV AC rms according to IEC | 40 mm | 3163.000 kg/km | 3705 kg/km | |
38107798 | 1x300 RM | U0/U: 12/20 kV AC rms according to IEC | 40 mm | 3274.000 kg/km | 3800 kg/km | |
38107799 | 1x400 RM | U0/U: 12/20 kV AC rms according to IEC | 43 mm | 4234.000 kg/km | 4519 kg/km | |
38107800 | 1x500 RM | U0/U: 12/20 kV AC rms according to IEC | 46 mm | 5194.000 kg/km | 5647 kg/km | |
38107801 | 1x630 RM | U0/U: 12/20 kV AC rms according to IEC | 48 mm | 6442.000 kg/km | 7049 kg/km | |
38107802 | 1x70 RM | U0/U: 18/30 kV AC rms according to IEC | 34 mm | 854.000 kg/km | 1656 kg/km | |
38107803 | 1x95 RM | U0/U: 18/30 kV AC rms according to IEC | 35 mm | 1094.000 kg/km | 1789 kg/km | |
38107804 | 1x120 RM | U0/U: 18/30 kV AC rms according to IEC | 37 mm | 1334.000 kg/km | 2048 kg/km | |
38107805 | 1x150 RM | U0/U: 18/30 kV AC rms according to IEC | 38 mm | 1723.000 kg/km | 2409 kg/km | |
38107806 | 1x240 RM | U0/U: 18/30 kV AC rms according to IEC | 42 mm | 2587.000 kg/km | 3382 kg/km | |
38107807 | 1x300 RM | U0/U: 18/30 kV AC rms according to IEC | 45 mm | 3163.000 kg/km | 4009 kg/km | |
38107808 | 1x400 RM | U0/U: 18/30 kV AC rms according to IEC | 48 mm | 4234.000 kg/km | 4934 kg/km | |
38107809 | 1x500 RM | U0/U: 18/30 kV AC rms according to IEC | 51 mm | 5194.000 kg/km | 6009 kg/km | |
38107810 | 1x630 RM | U0/U: 18/30 kV AC rms according to IEC | 51 mm | 6442.000 kg/km | 7423 kg/km | |
3828017 | 1x95 RM | U0/U: 12/20 kV AC rms according to IEC | 31 mm | 1094.000 kg/km | 1554 kg/km |