ÖLFLEX® CLASSIC 100 H 3G6
Power cable; 3G6; 12.7 mm; U0/U: 450 / 750 V; HFFR; Core identification: Colours; Flexible

Benefits
- Easy handling and installation due to very flexible design
- Halogen free and highly flame retardant materials reduce the risk of flame propagation, high smoke density and toxic flue gases in the event of a fire.
- Classified fire behaviour according to EU Directive 305/2011 (BauPVO/CPR) with article number selection at www.lappkabel.de/cpr.
- High electrical safety thanks to 4000 V test voltage.
- High oil resistance according to DIN EN 50363-4-1 (TM5), as well as UL OIL RES I and OIL RES II.
- VDE-tested fire behaviour.
Applications
- For building cabling to meet special fire protection requirements.
- For universal use for wiring of cross-plant control circuits and control circuits inside machines.
- For circuits that require a higher nominal voltage due to their installation.
- Cable design suitable for torsion applications in wind turbines.
- For fixed installation and occasional flexing without tensile strain.
- Can be used in dry and damp rooms.
- Suitable for medium mechanical stress.
- The HFFR outer sheath is highly resistant to acids and alkalis.
- Flexible use at temperatures down to -30°C.
Technical Attributes
General Information
Brand
ÖLFLEX®
Product type
Power cable
weight
0.320 kg
Copper index (lb)
1161.160 lb
copper index
172.800 kg
Electrical Characteristics
Nominal voltage
U0/U: 450 / 750 V AC rms after IEC
Nominal voltage fixed installation
U0/U: 0,6 / 1 kV AC rms after IEC
Test voltage
4 kV
Product Design
Cable dimension
3G6
Nominal conductor cross-section (mm2)
6 mm²
Conductor material
Bare Copper
conductor design
IEC 60228 class 5: fine-wire
Including protective conductor
Yes
Number of cores
3
Type of stranding
Twisted into layers
Shielded
No
Nominal outer diameter
12.7 mm
Shape of cable
Round
Core insulation base material
Halogen-free compound
Core insulation basic material, short form
HFFR
Base material outer sheath
Halogen-free compound
Basic material of outer sheath, short form
HFFR
Outer sheath colour
Grey
Core identification
Colours
core colour code
VDE 0293-308 (LAPP appendix T9)
Product Characteristics
Application type
FlexibleFixed Installation
For torsional load
Yes
Minimum bending radius, fixed installation
4 x outer diameter
Minimum bending radius in mm, fixed installation
50.8 mm
Minimum bending radius, occasionally moved
15 x outer diameter
Minimum bending radius in mm, occasionally moved
190.5 mm
torsion
for +/- 150 °/m and min. 5 °C up to 5000 Torsion cyclesfor +/- 150 °/m and min. -40 °C up to 2000 Torsion cycles
Temperature, fixed installation
-40 °C to 80 °C
Temperature, occasional flexing
-30 °C to 70 °C
Flame-retardant
Yes
Flame retardance according to
IEC 60332-3-24
Low smoke density according to
IEC 61034-2
low toxicity of combustion gases
NES 02-713 (≤ 3)
Corrosiveness of combustion gases according to
IEC 60754-2
UV-resistant
No
ozone resistant
Yes
Ozone-resistant according to
EN 50396, method B
Halogen-free
Yes
Zero halogen according to
IEC 60754-1
Oil resistant
Yes
Oil resistance according to
EN 50363-4-1: TM5UL OILRES IUL OILRES II
PWIS-free
Yes
Certifications and Standards
CE marking
Yes
UKCA marked
Yes
EAC certified
Yes
EAC certification number
ЕАЭС N RU Д-DE.АЮ64.В.00130/20
UL recognised
No
UL listed
No
cUR recognised
No
cUL listed
No
CSA certified
No
VDE certified
No
DNV/GL certified
No
CPR fire behaviour classified
B2ca
CPR smoke density
s1a
CPR drip behaviour
d1
CPR acidity
a1
Flame retardance tested according to UN/ECE-R118
No
Fire protection tested for rail vehicles
No
Documentation
-
Notes
- Photographs and graphics are not to scale and do not represent detailed images of the respective products.
- Please find our standard lengths at: www.lappkabel.de/kabel-standardlaengen.
- Unless specified otherwise, the product values shown are rated values at room temperature. You can receive further values, such as tolerances, upon request if they available and have been released for publication.
Product Family List
All articles from ÖLFLEX® CLASSIC 100 H
Article number | copper index | weight | Nominal outer diameter | Number of cores | Including protective conductor | Nominal conductor cross-section (mm2) |
---|---|---|---|---|---|---|
0014151 | 43.200 kg | 0.113 kg | 8.3 mm | 3 | Yes | 1.5 mm² |
0014152 | 57.600 kg | 0.139 kg | 9.0 mm | 4 | Yes | 1.5 mm² |
0014153 | 72.000 kg | 0.175 kg | 10.1 mm | 5 | Yes | 1.5 mm² |
0014157 | 72.000 kg | 0.166 kg | 9.7 mm | 3 | Yes | 2.5 mm² |
0014166 | 172.800 kg | 0.320 kg | 12.7 mm | 3 | Yes | 6.0 mm² |
0014180 | 1680.000 kg | 2.487 kg | 32.3 mm | 5 | Yes | 35.0 mm² |
Why Choose LAPP?
LAPP manufactures the highest quality cable, connectors, glands and industrial communication solutions to enhance factory automation and future-ready industrial manufacturing production systems and equipment. LAPP's state of the art manufacturing plant headquartered in Florham Park, N.J. includes an inhouse UL Client Data Program and UL certified laboratory to ensure the highest quality.